Using Weather and Schedule based Pattern Matching and Feature based PCA for Whole Building Fault Detection — Part II Field Evaluation

Publication Type

Journal Article

Date Published

03/2022

Authors

DOI

Abstract

In a heating, ventilation and air conditioning (HVAC) system, a whole building fault (WBF) refers to a fault that occurs in one component but may trigger additional faults/abnormalities on different components or subsystems resulting in significant impacts on the energy consumption or indoor air quality in buildings. At the whole building level, interval data collected from various components/subsystems can be employed to detect WBFs. In the Part I of this study, a novel data-driven method which includes weather and schedule-based Pattern Matching (WPM) procedure and a feature based principal component analysis PCA (FPCA) procedure was developed to detect the WBF. This article is the second of a two-part study of the development of the whole building fault detection method. In the Part II of the study (this paper), various WBFs were designed and imposed in the HVAC system of a campus building. Data from both imposed fault and naturally-occurred faults were collected through the Building Automation System to evaluate the developed fault detection method. Evaluation results show that the developed WPM-FPCA method reaches a satisfactory detection rate (85% and 100% under two principal component retention rates) and a 0% false alarm rate (under two principal component retention rates).

Journal

Journal of Engineering for Sustainable Buildings and Cities

Year of Publication

2022

Organization

Research Areas

Related Files