Harmonics from Compact Fluorescent Lamps

Publication Type

Conference Paper

Authors

Abstract

Measured characteristics of compact fluorescent lamps (CFL) and incandescent lamps with diode type devices show low power factor (47% to 67%) and/or high total harmonic distortion (>100% THD). There is little effect on a building power quality if the CFL comprise less than 10% of the buildings load. Even if the load due to CFL is as high as 26% of the buildings total, the voltage distortion is less than 5%. Circuits along with estimated costs are presented that correct for power factor and suppress the harmonics.

Journal

Annual IEEE-IAS Conference

Year of Publication

1991

Organization

Research Areas

Related Files